Cell cooling towers
M-CTI cell cooling towers in the glass-fibre reinforced plastic MNK-MAXI range
The “MNK-MAXI” series represents our most powerful cooling towers. They are designed to meet the requirements in heavy industry.
More than a quarter of a century of experience reflects our design of cooling towers. Today, we build these large cooling tower units in the shape of a framework using our own GRP profiles. This guarantees many years of corrosion-free operation.
Depending on the requirements of our customers, the plant shut down period for our cell cooling towers in the MNK-MAXI series can be reduced to just a few days. We first assemble the new cooling tower next to your old system. With a specially designed hoist, we then position it on the existing cooling tower basin, for example.
Cell cooling towers in detail:
- Structure made of GRP profiles
- Stainless steel hardware
- GRP cladding
- Cooling tower deck made of GRP panels with anti-slip coating
- Guard rails made of GRP profiles
- Staircases and cage ladders made of GRP profiles
- Drift eliminators made of PP material
- Flanged water distribution made from PP material
- High-performance cooling fill made of PP or PVC
The mechanical part of the cooling towers
- Induced fans with blades made from GRP or aluminium
- Fanstacks made of reinforced GRP partitions with stainless steel hardware
- Bevel helical gearbox with recirculating oil lubrication system
- All-steel couplings in stainless steel with composite spacer sleeves for connection to motor and gearbox
- Drive motors in cooling tower design
The advantages of induced draft cell cooling towers
- No corrosion
- Strong structure
- Short installation times
- Fast availability
- Short downtimes for servicing work
- Cost-optimisation
Technical data
MNK | 640 | 800 | 1.000 | 1.200 | 1.440 |
Length in mm | 8.000 | 8.000 | 10.000 | 10.000 | 12.000 |
Width in mm | 8.000 | 10.000 | 10.000 | 12.000 | 12.000 |
Water inlet height in mm | 5.600 | 5.600 | 6.000 | 6.000 | 6.800 |
Height of air intake in mm and number of intakes | 2.600/2 | 2.600/2 | 3.000/2 | 3.000/2 | 3.800/2 |
Fan deck height | 7.500 | 7.600 | 8.100 | 8.300 | 9.100 |
Diameter of fan | 4.870 | 5.545 | 6.090 | 6.700 | 7.310 |
Total height incl. fan stack in mm max. | 11.700 | 11.800 | 12.300 | 12.500 | 13.300 |
Circulating volume in m³/hr | 400 - 1.800 | 500 - 2.200 | 600 - 2.600 | 700 - 3.200 | 800 - 4.100 |
Technical data
MNK | 1.680 | 1.960 | 2.240 | 2.560 |
Length in mm | 12.000 | 14.000 | 14.000 | 16.000 |
Width in mm | 14.000 | 14.000 | 16.000 | 16.000 |
Water inlet height in mm | 6.800 | 6.800 | 7.500 | 7.500 |
Height of air intake in mm and number of intakes | 3.800/2 | 3.800/2 | 4.500/2 | 4.500/2 |
Fan deck height | 9.500 | 9.700 | 10.500 | 10.700 |
Diameter of fan | 7.920 | 8.530 | 9.140 | 10.360 |
Total height incl. fan stack in mm max. | 13.700 | 13.900 | 14.700 | 14.900 |
Circulating volume in m³/hr | 900-4.800 | 1.000-5.600 | 1.100-6.600 | 1.200-7.400 |